The Complete Guide To Sungrow Inverter Error Codes

All 80 Sungrow error codes in plain English, from Fault 002 to Fault 1616: what each one means, how urgent it is, how to reset your inverter safely, and whether it can be repaired.

Jump to the 80 Sungrow error codes

Why a Sungrow error code is worth sorting now

When a Sungrow shows a fault number, it has usually stopped feeding power into the house. Every sunny hour it stays that way, you buy back from the grid what your panels should have made. Some Sungrow faults matter for more than the bill: a low insulation or earth fault means live solar wiring is leaking to earth somewhere, and an arc fault is a fire risk.

Sungrow is one of the easier brands to get sorted. It is supported in Australia with a local service team, and we install Sungrow ourselves, so we know these units well. Most faults are repairable, and many are not the inverter at all: the street voltage running high on a sunny afternoon, a tripped switch or a damp connector.

Caught early, a Sungrow fault is usually a short visit and a clear fix. Left to repeat, a voltage trip that costs you an hour a day adds up over a summer, and a small leak to earth can get worse with every rain.

Find your code in the table below to see what it means and how urgent it is. If your home is in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland, our own licensed electricians will go through it with you over the phone for free before anyone drives out. Check your postcode to see if we cover you.

Which Sungrow inverter do you have?

The model is on the label on the side of the unit, and in the iSolarCloud app if your system is connected to it. A model name starting SG is a string inverter without a battery; SH is a hybrid.

  • SG RS (SG2.0RS-S to SG6.0RS): the home string inverter range, and where most codes on this page come from. Supported, and usually repairable.
  • SH RS hybrid (SH3.0RS to SH6.0RS): the hybrid range that runs a battery and a backup circuit. The battery and backup codes, such as 051, 323 and 714, apply to these.
  • SG KTL: Sungrow's three-phase string inverter range. Supported.
  • SG2K-S, SG3K-D and SG5K-D: two of the codes on this page come from a secondary copy of their manual. Supported.

All 80 Sungrow error codes, explained

Sungrow shows a fault as a number, written Fault 039, Error 39 or just 039 depending on where you read it, so the table lists every code with its leading zeros. Some numbers stand for a family: Fault 532 is string 1, 533 string 2 and so on, and the row says so. Every code is below, grouped by what it relates to: the grid and mains supply, the panel input and power output, insulation and earth faults, heat and cooling fans, the unit's internal hardware, the battery, and monitoring. The number in brackets after each code's name is its source in the reference list.

  • Stop and call A safety or hardware fault that nobody can fix from a phone. Do the one safe restart at most, then call.
  • Worth a look Something to check or restart safely. If it comes back, book a visit.
  • Wait and watch The inverter has paused for a reason outside itself, usually the grid or the light, and restarts on its own.

We always err on the cautious side: when a code sits between two ratings, it gets the higher one.

Grid and mains supply error codes 19 codes

The mains grid coming into the unit: voltage, frequency and outages. Many of these are the grid, not the inverter, and clear on their own. 4 stop and call, 15 wait and watch.

Error codeWhat it meansWhat to do
Fault 002Sungrow Fault 002 Grid overvoltage[1]

The mains voltage at your switchboard went above the limit the inverter is allowed to run at, which is common on sunny afternoons when the street is exporting a lot of solar. The inverter switches off to protect itself and reconnects once the voltage settles.

Safe steps in the lookup
Wait and watch
Fault 003Sungrow Fault 003 Grid transient overvoltage[1]

A very short spike in the mains voltage tripped the inverter. It is a grid event, not a fault in the inverter, and it reconnects by itself once the grid is steady.

Safe steps in the lookup
Wait and watch
Fault 004Sungrow Fault 004 Grid undervoltage[1]

The mains voltage dropped below the inverter's lower limit, often during a brown-out, a partial outage or heavy load on the street. The inverter waits for the grid to return to normal and then reconnects.

Safe steps in the lookup
Wait and watch
Fault 005Sungrow Fault 005 Grid voltage too low[1]

A deeper or very brief drop in mains voltage than code 004. The grid is the cause and the inverter reconnects once the supply is steady.

Safe steps in the lookup
Wait and watch
Fault 008Sungrow Fault 008 Grid overfrequency[1]

The mains frequency went above the inverter's limit. This is a grid event and the inverter reconnects once the frequency returns to normal.

Safe steps in the lookup
Wait and watch
Fault 009Sungrow Fault 009 Grid underfrequency[1]

The mains frequency dropped below the inverter's limit. This is a grid event and the inverter reconnects once the frequency returns to normal.

Safe steps in the lookup
Wait and watch
Fault 010Sungrow Fault 010 No grid connection[1]

The inverter cannot see the mains supply, so it has shut down. Either the power is out in your area, the solar supply main switch or AC breaker has tripped, or an AC connection has failed. It reconnects by itself once it sees the grid again.

Safe steps in the lookup
Wait and watch
Fault 013Sungrow Fault 013 Grid abnormal[1]

The inverter saw something wrong with the mains during its checks before connecting, such as unstable supply, a loose AC cable or live and neutral swapped. It reconnects once the grid reads normally.

Safe steps in the lookup
Wait and watch
Fault 014Sungrow Fault 014 Ten minute grid overvoltage[1]

The average mains voltage over ten minutes was above the limit set by AS/NZS 4777, which is very common in Australian streets with lots of solar. The inverter reconnects once the average drops, but if it happens most days you lose production.

Safe steps in the lookup
Wait and watch
Fault 015Sungrow Fault 015 High grid voltage[1]

A higher grid overvoltage trip than code 002. The mains voltage at the inverter rose well above the limit, which can be the street voltage or an undersized or long AC cable adding voltage rise. The inverter reconnects when the voltage drops.

Safe steps in the lookup
Wait and watch
Fault 017Sungrow Fault 017 Grid voltage imbalance[1]

On a three-phase supply, the voltages on the three phases are too far apart for the inverter to run. It is a grid condition and the inverter reconnects when the phases balance.

Safe steps in the lookup
Wait and watch
Fault 071Sungrow Fault 071 AC surge protector alarm[2]

The surge protection device on the inverter's AC side has worn out or failed, often after a lightning storm or a grid surge. The inverter keeps producing but is no longer protected until the module is replaced. Internal and hardware faults need testing with the right instruments, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 072Sungrow Fault 072 DC surge protector alarm[2]

The surge protection device on the inverter's solar (DC) side has worn out or failed, often after a lightning storm. The inverter keeps producing but is no longer protected until the module is replaced. Internal and hardware faults need testing with the right instruments, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 101Sungrow Fault 101 High grid frequency[2]

The mains frequency went above the inverter's upper limit. It is a grid event and the inverter reconnects once the frequency settles.

Best effort · from a secondary copySafe steps in the lookup
Wait and watch
Fault 102Sungrow Fault 102 Low grid frequency[2]

The mains frequency dropped below the inverter's lower limit. It is a grid event and the inverter reconnects once the frequency settles.

Best effort · from a secondary copySafe steps in the lookup
Wait and watch
Fault 108Sungrow Fault 108 AC side undervoltage[2]

The voltage on the inverter's AC side dropped below its limit. It usually behaves like a grid undervoltage and clears when the supply recovers; Sungrow's current manuals list it in the system fault group, so a repeat with the grid normal needs a check.

Best effort · from a secondary copySafe steps in the lookup
Wait and watch
Fault 109Sungrow Fault 109 AC side overvoltage[2]

The voltage on the inverter's AC side went above its limit. It usually behaves like a grid overvoltage and clears when the voltage settles; Sungrow's current manuals list it in the system fault group, so a repeat with the grid normal needs a check.

Best effort · from a secondary copySafe steps in the lookup
Wait and watch
Fault 323Sungrow Fault 323 Grid on the backup port[1]

The hybrid inverter is in backup mode but can see the mains on a port that should be isolated, which means the backup and grid wiring are connected together somewhere. It is a wiring fault that needs an electrician.

Safe steps in the lookup
Stop and call
Fault 500Sungrow Fault 500 Surge protector or fuse alarm[2]

The inverter's surge protection or an internal fuse is showing abnormal, often after a storm or on a hybrid with a loose battery DC cable. Production usually continues, but the protection needs checking. Internal and hardware faults need testing with the right instruments, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call

Panel input and power output error codes 7 codes

The DC input from the panels and the power the unit puts out: string voltage, low light, overloads and output limits. 5 stop and call, 2 worth a look.

Error codeWhat it meansWhat to do
Fault 028Sungrow Fault 028 PV1 reverse connection[1]

The solar string on input 1 is wired with positive and negative swapped. The inverter will not run it, and the connectors must only be unplugged by an electrician once the string current has dropped.

Safe steps in the lookup
Stop and call
Fault 029Sungrow Fault 029 PV2 reverse connection[1]

The solar string on input 2 is wired with positive and negative swapped. The inverter will not run it, and the connectors must only be unplugged by an electrician once the string current has dropped.

Safe steps in the lookup
Stop and call
Fault 051Sungrow Fault 051 Backup load overpower[4]

On a hybrid inverter running the house from the battery, the appliances on the backup circuit are drawing more than the inverter can supply. Turning off heavy appliances lets it recover.

Safe steps in the lookup
Worth a look
Fault 203Sungrow Fault 203 PV voltage too high[2]

The solar string voltage is higher than the inverter's internal bus can accept, which normally means too many panels in series for this inverter. Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 532Sungrow Fault 532 String reverse polarity alarm[1]

One solar string (532 is string 1, 533 string 2 and so on) is connected with positive and negative swapped. The inverter will not use that string, and the connectors must only be unplugged by an electrician once the string current has dropped.

Safe steps in the lookup
Stop and call
Fault 548Sungrow Fault 548 PV string abnormal[1]

One solar string (548 is string 1, 549 string 2 and so on) is producing much less than expected. Shading, dirt, a loose connector, a blown string fuse or a failing panel are the usual causes. The inverter keeps running on the other strings.

Safe steps in the lookup
Worth a look
Fault 1600Sungrow Fault 1600 PV grounding fault[1]

The inverter detected a solar string shorted to earth (1600 is string 1, 1601 string 2 and so on). This is a serious safety fault: Sungrow says the DC isolator must not be opened and the faulty string must not be reconnected until an electrician has cleared the fault.

Safe steps in the lookup
Stop and call

Panels, insulation and earth faults error codes 10 codes

Insulation, earth and leakage faults on the solar panel side. These are safety faults: live DC wiring may be leaking to earth somewhere on the roof. 10 stop and call.

Error codeWhat it meansWhat to do
Fault 012Sungrow Fault 012 Excess leakage current[1]

The inverter detected current leaking to earth from the solar wiring, which is a safety trip. Damp weather or poor sunlight can cause it and it may clear when things dry out, but a repeat means the cables or connectors need testing.

Safe steps in the lookup
Stop and call
Fault 039Sungrow Fault 039 Low insulation resistance[1]

The inverter measured too little insulation between the solar wiring and earth before it would start, which is a safety trip. Moisture in a connector or junction box after rain, a damaged cable, or a cracked panel are the usual causes. It may clear on a dry day, but a repeat needs testing.

Safe steps in the lookup
Stop and call
Fault 041Sungrow Fault 041 Leakage current sensor fault[1]

The circuit that watches for current leaking to earth failed its self-test, so the inverter cannot be sure its safety protection works and stays off. Sungrow lists it as a system fault that needs a service call if a restart does not clear it.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 056Sungrow Fault 056 Leakage current over limit (second processor)[5]

The inverter's backup processor detected current leaking to earth from the solar wiring. Treat it the same as code 012: a safety trip that needs the strings tested if it repeats.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 087Sungrow Fault 087 Arc detection self-test fault[1]

The circuit that watches for electrical arcing in the solar wiring failed its own self-test, so the inverter cannot rely on that safety function. Sungrow lists it as a system fault that needs service if a restart does not clear it.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 088Sungrow Fault 088 Electric arc fault[1]

The inverter detected electrical arcing in the solar DC wiring, which is a fire risk, and has shut down. A loose or corroded connector, a damaged cable or a failing panel junction box is the usual cause. It must not simply be cleared and restarted until the wiring has been inspected.

Safe steps in the lookup
Stop and call
Fault 089Sungrow Fault 089 Arc detection switched off[1]

The inverter's arc fault detection has been turned off in the settings, so it warns you that this safety function is not active. Production continues; the installer can turn it back on. Arc faults are a fire risk, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 106Sungrow Fault 106 Earth connection fault[1]

The inverter cannot see a proper earth connection, so it refuses to run. A loose or missing earth or neutral at the inverter or switchboard, or a problem with the main earth link, is the usual cause. It is a safety fault that needs an electrician.

Safe steps in the lookup
Stop and call
Fault 302Sungrow Fault 302 Low PV insulation resistance[2]

On hybrid inverters, the solar wiring measured too little insulation to earth, the same safety trip as code 039. Moisture in a connector or isolator after rain or a damaged cable are the usual causes.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 320Sungrow Fault 320 Leakage current sensor self-test[2]

The sensor that watches for current leaking to earth failed its self-test, so the inverter will not run without that protection. Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call

Heat and cooling fans error codes 6 codes

Over-temperature, heat derating and the cooling fans. Heat faults are taken seriously: a unit that cannot cool itself can be a fire risk. 5 stop and call, 1 worth a look.

Error codeWhat it meansWhat to do
Fault 036Sungrow Fault 036 Inverter over temperature[3]

The inverter's heatsink or power module is too hot, so it has cut back or stopped until it cools. Direct sun on the unit, a blocked vent, a dead fan or a very hot day are the usual causes. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 037Sungrow Fault 037 Ambient temperature too high[1]

The air around or inside the inverter is hotter than it is rated for, so it has reduced output or stopped until it cools. It restarts by itself once the temperature drops, but a poorly placed inverter will keep doing this all summer. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Safe steps in the lookup
Stop and call
Fault 043Sungrow Fault 043 Ambient temperature too low[1]

The inverter is colder than its minimum operating temperature (about minus 25 degrees), so it will not start. It is rare in Australia and the inverter can be restarted once the day warms up.

Safe steps in the lookup
Worth a look
Fault 070Sungrow Fault 070 Fan fault[1]

The inverter's cooling fan is not running properly, either blocked or worn out. The inverter keeps running but will overheat and cut back on hot days until the fan is cleaned or replaced. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Safe steps in the lookup
Stop and call
Fault 503Sungrow Fault 503 Temperature sensor alarm[2]

One of the inverter's temperature sensors reads open or short circuit (503 and 504 ambient, 505 and 506 internal). The inverter keeps producing but may cut back wrongly on warm days until the sensor is fixed. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 513Sungrow Fault 513 Fan stall alarm[2]

The cooling fan is running slow (512) or has stalled (513). The inverter keeps producing but will overheat and cut back on hot days until the fan is cleaned or replaced. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call

Internal hardware and safety checks error codes 30 codes

The unit's own electronics: relays, sensors, the DC bus, memory and its self-checks. Nearly all of these need an electrician. 29 stop and call, 1 wait and watch.

Error codeWhat it meansWhat to do
Fault 006Sungrow Fault 006 AC output overcurrent[3]

The current the inverter was pushing into the grid went above its protection limit, usually because of a disturbance on the grid. It starts again on its own once the current drops back. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 007Sungrow Fault 007 Transient AC overcurrent[3]

A brief surge of output current tripped the inverter. It recovers by itself within seconds, and Sungrow's current manuals treat it as a general system fault if it keeps returning. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 011Sungrow Fault 011 DC injection too high[3]

The inverter measured too much DC in the current it sends to the grid. It usually clears itself; if it keeps returning it points to a problem inside the inverter. DC on the AC side is a protection fault, so we treat it as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 016Sungrow Fault 016 Bus voltage or power high[1]

The voltage on the inverter's internal DC bus went above its limit, usually because the solar string voltage is high on a cold bright morning or the array is oversized for the inverter. Sungrow lists it as a system fault.

Safe steps in the lookup
Stop and call
Fault 019Sungrow Fault 019 Bus transient overvoltage[1]

A short spike on the inverter's internal DC bus tripped it. Older Sungrow manuals call this a transient bus overvoltage that clears itself; the current manual lists it as a system fault, and Sungrow Australia links a repeating 019 to a possible solar string short to earth.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 020Sungrow Fault 020 Bus overvoltage[1]

The inverter's internal DC bus voltage is too high, most often because the solar string voltage exceeds what the inverter can take. Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 021Sungrow Fault 021 PV1 input overcurrent[3]

Too much current is coming in on solar input 1, which usually means more strings or panels are wired to that input than it is rated for, or there is a wiring problem on that side of the roof. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 022Sungrow Fault 022 PV2 input overcurrent[3]

Too much current is coming in on solar input 2, which usually means more strings or panels are wired to that input than it is rated for, or there is a wiring problem on that side of the roof. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 038Sungrow Fault 038 Grid relay fault[1]

The relay that connects the inverter to the grid failed its self-check. On SG inverters this is normally a hardware fault inside the unit; on SH hybrids it can also be caused by backup and grid wiring being mixed.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 040Sungrow Fault 040 Overcurrent or overvoltage protection[1]

An AC or DC overcurrent, or a DC overvoltage, tripped the inverter's protection. Sungrow lists it as a system fault, and Sungrow Australia links a repeating 040 to a possible solar string short to earth.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 044Sungrow Fault 044 Inverter self-test fault[1]

The inverter's power stage failed its own start-up self-test. Sungrow lists it as a system fault: a restart is worth one try, and a repeat means the unit needs service.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 045Sungrow Fault 045 PV1 boost circuit fault[1]

The part of the inverter that steps up the voltage from solar input 1 has a fault. It is internal hardware and Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 046Sungrow Fault 046 PV2 boost circuit fault[1]

The part of the inverter that steps up the voltage from solar input 2 has a fault. It is internal hardware and Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 048Sungrow Fault 048 Current sampling channel fault[1]

One of the inverter's internal current measurement circuits is reading wrongly. It is internal hardware and Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 053Sungrow Fault 053 Grid voltage over limit (second processor)[5]

The inverter's backup processor also saw the mains voltage go above the protection limit. It behaves like code 002: a grid condition that clears when the voltage settles.

Best effort · from a secondary copySafe steps in the lookup
Wait and watch
Fault 059Sungrow Fault 059 Internal processor communication[1]

The two processors inside the inverter stopped talking to each other. Sungrow lists it as a system alarm, so the inverter may keep running, but a repeat after a restart means it needs service.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 064Sungrow Fault 064 Inverter overvoltage fault[1]

An internal overvoltage trip on the inverter's output stage. Sungrow's current manuals list 064 only as a system fault: one restart is reasonable, and a repeat needs a service visit. On hybrid inverters it has also been linked to unbalanced backup loads or a changeover switch problem.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 067Sungrow Fault 067 Inverter instantaneous overvoltage[1]

A very short internal overvoltage trip on the inverter's output stage. Sungrow's current manuals list 067 only as a system fault: one restart is reasonable, and a repeat needs a service visit. Sungrow Australia has also linked it to mismatched or outdated firmware.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 084Sungrow Fault 084 Meter or CT reversed[1]

The energy meter or current clamp that tells the inverter which way power is flowing is wired backwards or on the wrong terminal. Production continues but export limits, battery charging and the app's import and export figures will be wrong. Wiring faults need an electrician, so we treat them as a call.

Safe steps in the lookup
Stop and call
Fault 100Sungrow Fault 100 AC output overcurrent protection[2]

The inverter's output current went above its hardware protection limit. It restarts on its own once the current drops back; Sungrow lists a repeat as a system fault. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 105Sungrow Fault 105 Grid protection self-test failed[2]

The inverter's grid-side protection failed its own self-check, so it will not connect to the mains. Sungrow lists it as a system fault: one restart is reasonable, and a repeat means the protection circuit needs service.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 107Sungrow Fault 107 DC injection overvoltage fault[2]

The inverter measured too much DC in the voltage it puts onto the grid and tripped its protection. Sungrow lists it as a system fault: one restart is reasonable, and a repeat points to a fault in the inverter's output stage.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 116Sungrow Fault 116 Internal system fault[1]

Sungrow does not publish a specific meaning for 116; it sits in the system fault group and the fault and alarm code list calls it a device abnormality. One full restart is reasonable, and a repeat means the inverter needs a service visit.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 200Sungrow Fault 200 Bus overvoltage hardware fault[2]

The inverter's internal DC bus went above its hardware limit, usually because the solar string voltage is too high for the inverter. Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 201Sungrow Fault 201 Bus undervoltage[2]

The inverter's internal DC bus voltage is too low, which can be very low solar input or a fault in the inverter. Sungrow lists it as a system fault.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 202Sungrow Fault 202 PV hardware overcurrent[2]

The current from the solar array hit the inverter's hardware protection limit. Sungrow lists it as a system fault: it usually means the array is delivering more current than the inverter's input is rated for.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 303Sungrow Fault 303 Bypass relay failure[2]

On a hybrid inverter, the relay that switches the house between grid and backup failed its check. It is usually caused by the backup and grid wiring being mixed or a changeover switch problem rather than the inverter itself.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 304Sungrow Fault 304 Backup relay failure[2]

On a hybrid inverter, the relay that feeds the backup circuit failed its check. Earthing or neutral problems on the backup circuit are a common cause.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 501Sungrow Fault 501 Memory read warning[2]

The inverter had trouble reading its internal memory. It keeps producing; a restart usually clears it and a repeat needs a service check. Internal and hardware faults need testing with the right instruments, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 1616Sungrow Fault 1616 System hardware fault[1]

A serious hardware fault inside the inverter. Sungrow says not to power the inverter up again and not to open the DC isolator while current is flowing: it needs a service visit.

Safe steps in the lookup
Stop and call

Battery error codes 4 codes

The battery, its management system and its state of charge. These only appear on systems with a battery connected. 3 stop and call, 1 worth a look.

Error codeWhat it meansWhat to do
Fault 703Sungrow Fault 703 Battery voltage fault[4]

The hybrid inverter sees the battery voltage outside its limits (703 low, 711 and 712 high, 715 hardware overvoltage, 717 a combined battery and BMS fault). A loose or reversed battery cable, a deeply drained battery or a faulty battery module are the usual causes.

Safe steps in the lookup
Stop and call
Fault 707Sungrow Fault 707 Battery temperature fault[4]

The battery is too hot (707) or too cold (708) to charge or discharge safely. It usually recovers on its own as the temperature changes; a battery in full sun or a hot enclosed space will keep doing this in summer. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Safe steps in the lookup
Stop and call
Fault 714Sungrow Fault 714 Battery communication fault[4]

The hybrid inverter has lost communication with the battery's management system, so it cannot charge or discharge the battery. A loose or damaged communication cable, or the battery being switched off, is the usual cause.

Safe steps in the lookup
Worth a look
Fault 716Sungrow Fault 716 Abnormal battery connection[4]

The battery power cable is reversed, loose or not connected, so the hybrid inverter will not use the battery. It is a wiring fault that needs an electrician.

Safe steps in the lookup
Stop and call

Monitoring, communication and settings error codes 4 codes

Monitoring, Wi-Fi, meters, communication between parts of the system, settings and firmware. Usually not a hardware fault, but the system may stop reporting. 1 stop and call, 3 worth a look.

Error codeWhat it meansWhat to do
Fault 047Sungrow Fault 047 PV input configuration mismatch[2]

The way the solar strings are physically connected does not match the input mode set in the inverter, for example strings paralleled onto an input set to independent. The installer needs to correct the setting or the wiring.

Best effort · from a secondary copySafe steps in the lookup
Worth a look
Fault 075Sungrow Fault 075 Parallel inverter communication[1]

Two or more inverters set up to work together have lost their communication link. Each unit usually keeps producing, but the shared control does not work until the cable or settings are fixed.

Safe steps in the lookup
Worth a look
Fault 085Sungrow Fault 085 Software version mismatch[2]

The firmware on the inverter's internal boards, or between the inverter and its battery or meter, does not match. The installer or Sungrow needs to update it; it is not something that clears on its own. Internal and hardware faults need testing with the right instruments, so we treat them as a call.

Best effort · from a secondary copySafe steps in the lookup
Stop and call
Fault 514Sungrow Fault 514 Meter communication lost[1]

The inverter has lost contact with the energy meter at the switchboard. Production continues, but export limiting and battery control rely on the meter, so the cable or meter needs checking.

Safe steps in the lookup
Worth a look

Got a Sungrow error code? Free phone diagnosis in our service area

Our own licensed electricians cover Greater Adelaide and regional SA, and from North Brisbane up through the Sunshine Coast to Gympie. Check your postcode, then read us the code and tell us the install year. If it needs a visit, the callout is credited against the work.

How to reset a Sungrow inverter safely

Try one restart, in this order:

  1. Switch the solar supply main switch off at the switchboard.
  2. Switch the DC isolator off at the inverter.
  3. Wait five minutes.
  4. Switch the DC isolator back on, then the solar supply main switch.

Never open the unit or touch the wiring. Never restart anything that smells hot or shows scorch marks. Do not restart at all for Fault 1600 or Fault 1616: Sungrow says not to open the DC isolator for these, so leave everything as it is and call. If any other code comes back after one restart, stop and call.

Sungrow inverter repair or replacement?

On a visit, our electricians test the whole system before they blame the Sungrow. That means insulation resistance on every string, earth continuity, the relay, DC string voltages and currents, the AC supply and the inverter's own fault record. A Fault 039 or 1600 is usually found on the roof, in a wet connector or a damaged cable, and the repair is to the wiring rather than the inverter.

Sungrow is supported here with a local service team, so an internal fault is usually a repair. If the unit is still under warranty, we check that first and tell you which way to go. If a unit does need replacing, we quote a straight replacement and a hybrid option side by side, and the callout comes off whichever you choose.

We do this work in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland only. Outside those areas, everything above still applies: take the code, its meaning and the urgency to a licensed electrician near you.

Where these Sungrow error codes come from

Every Sungrow code on this page was read from the maker's own manual wherever one survives (43 per cent of them). Where only a secondary copy survives, the row says "best effort" and so does the lookup. The numbers match the references in the code table.

  1. [1]
    Sungrow SG2.0RS-S to SG6.0RS user manual44 codes, 29 of 44 from the maker's own document
  2. [2]
    Sungrow Communication Protocol of Residential Hybrid Inverter V1.1.11 (2025-11)23 codes, best effort, from a secondary copy
  3. [3]
    Sungrow three-phase SG-KTL user manual excerpt6 codes, best effort, from a secondary copy
  4. [4]
    Sungrow SH3.0RS to SH6.0RS hybrid user manual5 codes, from the maker's own document
  5. [5]
    Solarmatic helpdesk: Sungrow SG2K-S/SG3K-D/SG5K-D errors (from the SG-K-D user manual)2 codes, best effort, from a secondary copy

Tables last updated

Sungrow error code questions, answered

How do I read a Sungrow error code?

Note the number, with or without the word Fault in front. The app, the manuals and other websites write the same code in different ways, so 39, 039 and Fault 039 are all one fault. Search the number, or a word like grid, fan or battery, in the table above to see what it means and how urgent it is.

What does Sungrow Fault 002 mean?

Fault 002 is “grid overvoltage”. The mains voltage at your switchboard went above the limit the inverter is allowed to run at, which is common on sunny afternoons when the street is exporting a lot of solar. The inverter switches off to protect itself and reconnects once the voltage settles. We rate it wait and watch. See it in the table.

What does Sungrow Fault 039 mean?

Fault 039 is “low insulation resistance”. The inverter measured too little insulation between the solar wiring and earth before it would start, which is a safety trip. Moisture in a connector or junction box after rain, a damaged cable, or a cracked panel are the usual causes. It may clear on a dry day, but a repeat needs testing. We rate it stop and call. See it in the table.

Do you cover my area?

We work in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland. Check your postcode to be sure. Outside those areas, this page still tells you what your code means and how urgent it is, and a licensed electrician near you can take it from there.

What does it cost to have a Sungrow looked at?

For homes in our service area, the phone diagnosis is free. If it needs a visit, there is a callout fee, and it is credited against any repair or replacement we do.

Will you work on a Sungrow you did not install?

Yes, if it is in our service area. Most of our repair work is on systems someone else installed. We test the whole system, not just the unit on the wall.

My Sungrow trips out on sunny afternoons. Is it faulty?

Usually not. Fault 002, 014 and 015 mean the grid voltage at your switchboard went above the limit, which is common in streets where a lot of homes export solar. The inverter reconnects on its own. If it happens most sunny days, note the times for us: it can often be fixed with settings or a network voltage adjustment.

Do you work on Sungrow hybrids with a battery?

Yes, in our service area. The SH hybrids have their own codes for the battery and the backup circuit, such as 703, 714 and 716 for the battery and 051 and 323 for backup. Several of these are a loose cable, a lost connection or mixed-up wiring rather than a failed battery, so we test before anything is replaced.

Where do the codes on this page come from?

Only 43 per cent of the Sungrow codes here are explained in Sungrow’s own user manuals. The rest are listed in Sungrow documents without a plain explanation, such as its communication protocol for hybrid inverters, or come from a manual excerpt and a helpdesk copy, so we have explained them as best we can and marked those rows best effort. Each code carries a numbered reference to its document in the source list.

Written by

Joe Deionno

Started in 2017 after years of subcontracting and seeing the dodgy operators at work; set out to be the installer people could trust. Oversees every install in both states.