The Complete Guide To Solis Inverter Error Codes

All 40 Solis error codes in plain English, from an OV-G-V grid trip to a PV ISO-PRO insulation fault: what each one means, how urgent it is, how to reset your inverter safely, and whether it can still be repaired.

Jump to the 40 Solis error codes

Why a Solis error code is worth sorting now

A Solis with an alarm on its screen has usually stopped sending power to your house. While it sits there, your roof makes nothing and every unit you use comes from the grid at full price. A few Solis alarms matter for safety as well as savings: ILeak-PRO and PV ISO-PRO mean the inverter has found the solar wiring leaking to earth, or the insulation that stops it failing.

Solis, also sold under the Ginlong name, has made inverters since 2013 and is supported in Australia through its local office. Some faults inside the unit can be repaired and some cannot, and the alarm is the first clue to which. Plenty of Solis alarms are not inverter faults at all: a high street voltage, a tripped breaker or a wet connector on the roof.

Sorted early, a grid trip is often a cable or a setting, and an insulation fault is often one connector. Ignored, the inverter keeps dropping out, the savings keep slipping, and a small wiring fault has time to become a bigger one.

Find your code in the table below to see what it means and how urgent it is. If your home is in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland, our own licensed electricians will go through it with you over the phone for free before anyone drives out. Check your postcode to see if we cover you.

Which Solis inverter do you have?

The model is on the label on the side of the unit, and in SolisCloud if your system reports there. Some units carry the Ginlong name instead: it is the same maker, so the alarms on this page apply.

  • S5-GR3P: the three-phase S5 range in Solis's installation manual. Alarms such as G-PHASE and PHASE-FAULT only appear on three-phase units like this one. Supported, and sometimes repairable.
  • Solis hybrids: run the panels and a battery together. The battery and backup alarms, NO-Battery, CAN_Comm_FAIL, OV-Vbatt and Over-Load, only appear on these. Supported, and sometimes repairable.
  • Ginlong and Ginlong Solis: the name on some Solis units, in service here since 2013. Look the alarm up here as normal.

All 40 Solis error codes, explained

Solis shows a fault as a short alarm name on the inverter's screen and in SolisCloud, such as OV-G-V for grid voltage too high or PV ISO-PRO for an insulation fault. Every code is below, grouped by what it relates to: the grid and mains supply, the panel input and power output, insulation and earth faults, heat and cooling fans, the unit's internal hardware, and the battery. The number in brackets after each code's name is its source in the reference list.

  • Stop and call A safety or hardware fault that nobody can fix from a phone. Do the one safe restart at most, then call.
  • Worth a look Something to check or restart safely. If it comes back, book a visit.
  • Wait and watch The inverter has paused for a reason outside itself, usually the grid or the light, and restarts on its own.

We always err on the cautious side: when a code sits between two ratings, it gets the higher one.

Grid and mains supply error codes 12 codes

The mains grid coming into the unit: voltage, frequency and outages. Many of these are the grid, not the inverter, and clear on their own. 4 stop and call, 2 worth a look, 6 wait and watch.

Error codeWhat it meansWhat to do
G-F-FLUSolis G-F-FLU Grid frequency unstable[1]

The grid frequency is jumping around and the inverter is waiting for it to steady. It reconnects by itself.

Safe steps in the lookup
Wait and watch
G-IMPSolis G-IMP Grid impedance too high[3]

The inverter measured too much resistance in the AC path to the grid, usually an undersized or long cable run to the switchboard or a poor connection. A one-off can clear itself, but if it keeps coming back the cabling needs an electrician.

Safe steps in the lookup
Worth a look
G-PHASESolis G-PHASE Three-phase grid unbalanced[1]

On a three-phase inverter, the voltages on the three phases are too far apart, or one phase is wired wrong or undersized. The inverter waits until the phases are balanced again.

Safe steps in the lookup
Worth a look
GRID-INTFSolis GRID-INTF Grid interference[1]

The inverter is seeing a rough or distorted mains waveform, often where several inverters share one line or there is noisy equipment nearby. The manual also lists internal damage as a cause, so if a restart does not clear it the inverter needs testing. Internal and hardware faults need testing with the right instruments, so we treat them as a call.

Safe steps in the lookup
Stop and call
IG-ADSolis IG-AD Grid current sampling error[1]

The circuit that measures the inverter's output current is giving bad readings. If a restart does not clear it the sensing circuit has failed.

Safe steps in the lookup
Stop and call
IGFOL-FSolis IGFOL-F Grid current tracking error[1]

The inverter's control circuit lost track of the grid current it was trying to match. If a restart does not clear it, the power board has a fault.

Safe steps in the lookup
Stop and call
NO-GRIDSolis NO-GRID No grid detected[1]

The inverter cannot see mains power on its AC side. Either the power is out, the solar supply main switch or breaker is off, or an AC connection has failed.

Safe steps in the lookup
Wait and watch
OV-G-FSolis OV-G-F Grid frequency too high[1]

The grid frequency went above the inverter's limit for a moment and it disconnected. It reconnects by itself once the grid is steady again.

Safe steps in the lookup
Wait and watch
OV-G-VSolis OV-G-V Grid voltage too high[1]

The mains voltage at the inverter went above the limit it is allowed to export at, so it disconnected to protect itself. It usually clears on its own when the grid settles; if it happens most sunny afternoons the cable run or the street voltage needs checking.

Safe steps in the lookup
Wait and watch
PHASE-FAULTSolis PHASE-FAULT Grid phase angle wrong[1]

On a three-phase inverter, the phases are not 120 degrees apart, which usually means the AC wiring is in the wrong order or a phase is missing. It needs an electrician to check the AC connection.

Safe steps in the lookup
Stop and call
UN-G-FSolis UN-G-F Grid frequency too low[1]

The grid frequency dipped below the inverter's limit and it disconnected. It reconnects by itself once the grid is steady again.

Safe steps in the lookup
Wait and watch
UN-G-VSolis UN-G-V Grid voltage too low[1]

The mains voltage dropped below the inverter's lower limit, so it stopped exporting. This is almost always the grid or a brownout and clears by itself.

Safe steps in the lookup
Wait and watch

Panel input and power output error codes 4 codes

The DC input from the panels and the power the unit puts out: string voltage, low light, overloads and output limits. 2 stop and call, 2 worth a look.

Error codeWhat it meansWhat to do
DC-INTFSolis DC-INTF Abnormal DC input current[1]

The current from the panels is not what the inverter expects, which usually means a damaged or loose DC connection. The DC wiring and connectors need checking by an electrician.

Safe steps in the lookup
Stop and call
OV-DCSolis OV-DC Panel voltage too high[1]

The voltage coming from the panels is above what the inverter can accept, which happens when too many panels are in one string, especially on cold clear mornings. The string design needs checking by an electrician.

Safe steps in the lookup
Worth a look
Over-LoadSolis Over-Load Backup circuit overloaded[1]

On a Solis hybrid, the appliances on the backup circuit are drawing more than the inverter can supply off the battery. Reduce what is on the backup circuit and restart.

Safe steps in the lookup
Worth a look
Reve-DCSolis Reve-DC DC string reversed[1]

A string from the panels is connected the wrong way round at the inverter. This is a wiring fault and must be corrected by an electrician.

Safe steps in the lookup
Stop and call

Panels, insulation and earth faults error codes 7 codes

Insulation, earth and leakage faults on the solar panel side. These are safety faults: live DC wiring may be leaking to earth somewhere on the roof. 7 stop and call.

Error codeWhat it meansWhat to do
AFCI-CheckSolis AFCI-Check Arc detector self-check failed[1]

The arc-fault detection module inside the inverter failed its own test. If a restart does not clear it the module has failed and needs a technician.

Safe steps in the lookup
Stop and call
ARC-FAULTSolis ARC-FAULT DC arc detected[1]

The inverter detected electrical arcing in the panel wiring, which is a fire risk. Leave the system off and have an electrician find the loose or damaged connection.

Safe steps in the lookup
Stop and call
ILeak-CheckSolis ILeak-Check Leakage sensor self-check failed[1]

The inverter's leakage-current sensor failed its own test at start-up. If a restart does not clear it the sensor or board inside has failed.

Safe steps in the lookup
Stop and call
ILeak-PROSolis ILeak-PRO Leakage current protection[1]

The inverter measured current leaking to earth from the solar wiring, usually damaged cable insulation, water in a connector, or a wiring problem on the AC side. Wet-morning alarms can be ageing panels, but any repeat needs an electrician because this is an electrical safety trip.

Safe steps in the lookup
Stop and call
L&PE FAULTSolis L&PE FAULT AC line to earth fault[1]

The inverter found a low resistance between the active and the earth on the AC side, which means a wiring or earth fault in the AC circuit. It needs an electrician.

Safe steps in the lookup
Stop and call
PV ISO-PROSolis PV ISO-PRO Panel insulation fault[1]

The inverter found too little insulation between the panel wiring and earth, usually water in a connector or isolator, a chafed cable or a damaged panel. Morning or wet-weather alarms that clear by midday point to moisture; a persistent one is a safety issue and needs an electrician.

Safe steps in the lookup
Stop and call
PvMidIsoSolis PvMidIso Panel mid-point insulation low[1]

The inverter found a low-insulation or earthed point part way along a panel string, often a wet connector or a damaged panel. Like any insulation fault, it needs testing by an electrician.

Safe steps in the lookup
Stop and call

Heat and cooling fans error codes 2 codes

Over-temperature, heat derating and the cooling fans. Heat faults are taken seriously: a unit that cannot cool itself can be a fire risk. 1 stop and call, 1 wait and watch.

Error codeWhat it meansWhat to do
OV-TEMSolis OV-TEM Inverter too hot[1]

The inverter's internal temperature went over its limit, so it cut back or stopped. Usually it is mounted in direct sun or a hot, closed space; it comes back once it cools, but if it happens on ordinary days the fan or heatsink needs a look. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call.

Safe steps in the lookup
Stop and call
UN-TEMSolis UN-TEM Inverter too cold[1]

The inverter is below its minimum operating temperature and is waiting to warm up. It clears itself once the day warms.

Safe steps in the lookup
Wait and watch

Internal hardware and safety checks error codes 12 codes

The unit's own electronics: relays, sensors, the DC bus, memory and its self-checks. Nearly all of these need an electrician. 11 stop and call, 1 worth a look.

Error codeWhat it meansWhat to do
12Power-FAULTSolis 12Power-FAULT Internal 12V supply fault[1]

The small power supply that runs the inverter's own electronics has failed. If a restart does not clear it the inverter needs repair.

Safe steps in the lookup
Stop and call
BoostFalSolis BoostFal DC boost circuit fault[1]

The circuit that lifts the panel voltage inside the inverter has failed its check. If a restart does not clear it, the inverter has an internal hardware fault.

Safe steps in the lookup
Stop and call
DCInj-FAULTSolis DCInj-FAULT DC injection too high[1]

The inverter is letting a small amount of DC into its AC output, which the grid rules do not allow. A one-off can clear with a restart; if it keeps coming back the output stage needs testing. DC on the AC side is a protection fault, so we treat it as a call.

Safe steps in the lookup
Stop and call
DSP-B-FAULTSolis DSP-B-FAULT Internal processor fault[1]

The inverter's two control processors have stopped talking to each other, or the control software is missing or does not match the hardware. If a restart does not clear it the control board has failed.

Safe steps in the lookup
Stop and call
IGBT-OV-ISolis IGBT-OV-I Power stage overcurrent[1]

The main switching transistors inside the inverter saw too much current. If a restart does not clear it the power board has failed.

Safe steps in the lookup
Stop and call
INI-FAULTSolis INI-FAULT Start-up fault[1]

The inverter's control processors did not agree with each other when it started up. If it stays stuck here after a restart the control board has a fault.

Safe steps in the lookup
Stop and call
OV-BUSSolis OV-BUS Internal DC bus overvoltage[1]

The voltage on the inverter's internal DC bus went too high. It can follow a string that is too long, but it is often a fault inside the inverter and needs testing.

Safe steps in the lookup
Stop and call
OV-G-ISolis OV-G-I Grid output overcurrent[1]

The inverter pushed more current into the grid than it is allowed to, often because the grid waveform is distorted or an AC connection is poor. A one-off clears itself; repeated alarms need a look at the AC side. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call.

Safe steps in the lookup
Stop and call
RelayChk-FAILSolis RelayChk-FAIL Output relay check failed[2][4]

The relay that connects the inverter to the grid failed its self-test. Solis says to check the AC wiring and earthing first, but a repeat usually means the relay or power board has failed, which is a job for an electrician.

Safe steps in the lookup
Stop and call
UN-BUSSolis UN-BUS Internal DC bus undervoltage[1]

The voltage on the inverter's internal DC bus is too low. The manual puts it down to internal damage or a wire that has come loose, so it needs the inverter opened and tested.

Safe steps in the lookup
Stop and call
UNB-BUSSolis UNB-BUS Internal DC bus unbalanced[1]

The two halves of the inverter's internal DC bus are not sitting at the same voltage, which points to a failing component inside. It needs the inverter tested by an electrician.

Safe steps in the lookup
Stop and call
FailsafeSolis Failsafe Export meter communication lost[1]

The inverter has lost contact with the export-limit meter or EPM device, so it stops or limits output to be safe. The meter cable or setting needs checking.

Safe steps in the lookup
Worth a look

Battery error codes 3 codes

The battery, its management system and its state of charge. These only appear on systems with a battery connected. 3 worth a look.

Error codeWhat it meansWhat to do
CAN_Comm_FAILSolis CAN_Comm_FAIL Battery communication fault[1]

On a Solis hybrid, the inverter has lost contact with the battery or the battery is reporting an alarm. The battery cable, settings or the battery itself need checking.

Safe steps in the lookup
Worth a look
NO-BatterySolis NO-Battery Battery not connected[1]

On a Solis hybrid, the inverter cannot see the battery. Usually the battery breaker or fuse has tripped or the battery is switched off.

Safe steps in the lookup
Worth a look
OV-VbattSolis OV-Vbatt Battery voltage out of range[1]

On a Solis hybrid, the battery voltage is higher or lower than the inverter expects. A restart may clear it, otherwise the battery and its settings need checking.

Safe steps in the lookup
Worth a look

Got a Solis error code? Free phone diagnosis in our service area

Our own licensed electricians cover Greater Adelaide and regional SA, and from North Brisbane up through the Sunshine Coast to Gympie. Check your postcode, then read us the code and tell us the install year. If it needs a visit, the callout is credited against the work.

How to reset a Solis inverter safely

Try one restart, in this order:

  1. Switch the solar supply main switch off at the switchboard.
  2. Switch the DC isolator off at the inverter.
  3. Wait five minutes.
  4. Switch the DC isolator back on, then the solar supply main switch.

Never open the unit or touch the wiring. Never restart anything that smells hot or shows scorch marks. If the code comes back after one restart, stop and call.

Solis inverter repair or replacement?

On a visit, our electricians test the whole system before blaming the Solis. That means insulation resistance on every string, earth continuity, the grid relay, DC string voltages and currents, the AC supply at the switchboard and the inverter's own alarm history. RelayChk-FAIL is a good example: Solis says to check the AC wiring and earthing first, and only a repeat points at the relay or power board. G-IMP is often the cable run to the switchboard rather than the inverter.

Solis is supported in Australia through its local office, so when the fault is inside the unit we check whether a repair is possible before anything else. Some are and some are not. If the inverter cannot be fixed, we quote a straight replacement and a hybrid option side by side, and the callout comes off whichever you choose. The panels usually stay.

We do this work in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland only. Outside those areas, everything above still applies: take the code, its meaning and the urgency to a licensed electrician near you.

Where these Solis error codes come from

Every Solis code on this page was read from the maker's own manual. The numbers match the references in the code table.

  1. [1]
  2. [2]
    Solis Inverter Alarm Codes (Complete List)1 code, from the maker's own document
  3. [3]
  4. [4]
    Solis service knowledge base1 code, from the maker's own document

Tables last updated

Solis error code questions, answered

How do I read a Solis error code?

Read the alarm name exactly as the screen or SolisCloud spells it, dashes included, because OV-G-V and UN-G-V are opposite problems. Type it into the search box above the table, or scroll to the group it belongs to. Each row gives the plain-English meaning and one of three urgency ratings.

What does Solis OV-G-V mean?

OV-G-V is “grid voltage too high”. The mains voltage at the inverter went above the limit it is allowed to export at, so it disconnected to protect itself. It usually clears on its own when the grid settles; if it happens most sunny afternoons the cable run or the street voltage needs checking. We rate it wait and watch. See it in the table.

What does Solis ILeak-PRO mean?

ILeak-PRO is “leakage current protection”. The inverter measured current leaking to earth from the solar wiring, usually damaged cable insulation, water in a connector, or a wiring problem on the AC side. Wet-morning alarms can be ageing panels, but any repeat needs an electrician because this is an electrical safety trip. We rate it stop and call. See it in the table.

Do you cover my area?

We work in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland. Check your postcode to be sure. Outside those areas, this page still tells you what your code means and how urgent it is, and a licensed electrician near you can take it from there.

What does it cost to have a Solis looked at?

For homes in our service area, the phone diagnosis is free. If it needs a visit, there is a callout fee, and it is credited against any repair or replacement we do.

Will you work on a Solis you did not install?

Yes, if it is in our service area. Most of our repair work is on systems someone else installed. We test the whole system, not just the unit on the wall.

Why does my Solis show OV-G-V on sunny afternoons?

The mains voltage at your inverter has gone above the limit it is allowed to export at, so it steps off the grid and reconnects once the voltage settles. Now and then is normal. If it happens most sunny afternoons, the cable run to the switchboard or the street voltage needs checking, and we test both on a visit.

Is a Solis worth repairing?

Sometimes. Solis is still supported here, so a fault inside the unit is worth checking before anything is replaced, and many Solis alarms are outside the inverter altogether. We will tell you on the phone what your alarm usually means, and price a replacement beside any repair that is still possible.