A Solis with an alarm on its screen has usually stopped sending power to your house. While it sits there, your roof makes nothing and every unit you use comes from the grid at full price. A few Solis alarms matter for safety as well as savings: ILeak-PRO and PV ISO-PRO mean the inverter has found the solar wiring leaking to earth, or the insulation that stops it failing.
Solis, also sold under the Ginlong name, has made inverters since 2013 and is supported in Australia through its local office. Some faults inside the unit can be repaired and some cannot, and the alarm is the first clue to which. Plenty of Solis alarms are not inverter faults at all: a high street voltage, a tripped breaker or a wet connector on the roof.
Sorted early, a grid trip is often a cable or a setting, and an insulation fault is often one connector. Ignored, the inverter keeps dropping out, the savings keep slipping, and a small wiring fault has time to become a bigger one.
Find your code in the table below to see what it means and how urgent it is. If your home is in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland, our own licensed electricians will go through it with you over the phone for free before anyone drives out. Check your postcode to see if we cover you.
The model is on the label on the side of the unit, and in SolisCloud if your system reports there. Some units carry the Ginlong name instead: it is the same maker, so the alarms on this page apply.
Solis shows a fault as a short alarm name on the inverter's screen and in SolisCloud, such as OV-G-V for grid voltage too high or PV ISO-PRO for an insulation fault. Every code is below, grouped by what it relates to: the grid and mains supply, the panel input and power output, insulation and earth faults, heat and cooling fans, the unit's internal hardware, and the battery. The number in brackets after each code's name is its source in the reference list.
We always err on the cautious side: when a code sits between two ratings, it gets the higher one.
The mains grid coming into the unit: voltage, frequency and outages. Many of these are the grid, not the inverter, and clear on their own. 4 stop and call, 2 worth a look, 6 wait and watch.
| Error code | What it means | What to do |
|---|---|---|
| G-F-FLUSolis G-F-FLU | Grid frequency unstable[1] The grid frequency is jumping around and the inverter is waiting for it to steady. It reconnects by itself. Safe steps in the lookup |
Wait and watch |
| G-IMPSolis G-IMP | Grid impedance too high[3] The inverter measured too much resistance in the AC path to the grid, usually an undersized or long cable run to the switchboard or a poor connection. A one-off can clear itself, but if it keeps coming back the cabling needs an electrician. Safe steps in the lookup |
Worth a look |
| G-PHASESolis G-PHASE | Three-phase grid unbalanced[1] On a three-phase inverter, the voltages on the three phases are too far apart, or one phase is wired wrong or undersized. The inverter waits until the phases are balanced again. Safe steps in the lookup |
Worth a look |
| GRID-INTFSolis GRID-INTF | Grid interference[1] The inverter is seeing a rough or distorted mains waveform, often where several inverters share one line or there is noisy equipment nearby. The manual also lists internal damage as a cause, so if a restart does not clear it the inverter needs testing. Internal and hardware faults need testing with the right instruments, so we treat them as a call. Safe steps in the lookup |
Stop and call |
| IG-ADSolis IG-AD | Grid current sampling error[1] The circuit that measures the inverter's output current is giving bad readings. If a restart does not clear it the sensing circuit has failed. Safe steps in the lookup |
Stop and call |
| IGFOL-FSolis IGFOL-F | Grid current tracking error[1] The inverter's control circuit lost track of the grid current it was trying to match. If a restart does not clear it, the power board has a fault. Safe steps in the lookup |
Stop and call |
| NO-GRIDSolis NO-GRID | No grid detected[1] The inverter cannot see mains power on its AC side. Either the power is out, the solar supply main switch or breaker is off, or an AC connection has failed. Safe steps in the lookup |
Wait and watch |
| OV-G-FSolis OV-G-F | Grid frequency too high[1] The grid frequency went above the inverter's limit for a moment and it disconnected. It reconnects by itself once the grid is steady again. Safe steps in the lookup |
Wait and watch |
| OV-G-VSolis OV-G-V | Grid voltage too high[1] The mains voltage at the inverter went above the limit it is allowed to export at, so it disconnected to protect itself. It usually clears on its own when the grid settles; if it happens most sunny afternoons the cable run or the street voltage needs checking. Safe steps in the lookup |
Wait and watch |
| PHASE-FAULTSolis PHASE-FAULT | Grid phase angle wrong[1] On a three-phase inverter, the phases are not 120 degrees apart, which usually means the AC wiring is in the wrong order or a phase is missing. It needs an electrician to check the AC connection. Safe steps in the lookup |
Stop and call |
| UN-G-FSolis UN-G-F | Grid frequency too low[1] The grid frequency dipped below the inverter's limit and it disconnected. It reconnects by itself once the grid is steady again. Safe steps in the lookup |
Wait and watch |
| UN-G-VSolis UN-G-V | Grid voltage too low[1] The mains voltage dropped below the inverter's lower limit, so it stopped exporting. This is almost always the grid or a brownout and clears by itself. Safe steps in the lookup |
Wait and watch |
The DC input from the panels and the power the unit puts out: string voltage, low light, overloads and output limits. 2 stop and call, 2 worth a look.
| Error code | What it means | What to do |
|---|---|---|
| DC-INTFSolis DC-INTF | Abnormal DC input current[1] The current from the panels is not what the inverter expects, which usually means a damaged or loose DC connection. The DC wiring and connectors need checking by an electrician. Safe steps in the lookup |
Stop and call |
| OV-DCSolis OV-DC | Panel voltage too high[1] The voltage coming from the panels is above what the inverter can accept, which happens when too many panels are in one string, especially on cold clear mornings. The string design needs checking by an electrician. Safe steps in the lookup |
Worth a look |
| Over-LoadSolis Over-Load | Backup circuit overloaded[1] On a Solis hybrid, the appliances on the backup circuit are drawing more than the inverter can supply off the battery. Reduce what is on the backup circuit and restart. Safe steps in the lookup |
Worth a look |
| Reve-DCSolis Reve-DC | DC string reversed[1] A string from the panels is connected the wrong way round at the inverter. This is a wiring fault and must be corrected by an electrician. Safe steps in the lookup |
Stop and call |
Insulation, earth and leakage faults on the solar panel side. These are safety faults: live DC wiring may be leaking to earth somewhere on the roof. 7 stop and call.
| Error code | What it means | What to do |
|---|---|---|
| AFCI-CheckSolis AFCI-Check | Arc detector self-check failed[1] The arc-fault detection module inside the inverter failed its own test. If a restart does not clear it the module has failed and needs a technician. Safe steps in the lookup |
Stop and call |
| ARC-FAULTSolis ARC-FAULT | DC arc detected[1] The inverter detected electrical arcing in the panel wiring, which is a fire risk. Leave the system off and have an electrician find the loose or damaged connection. Safe steps in the lookup |
Stop and call |
| ILeak-CheckSolis ILeak-Check | Leakage sensor self-check failed[1] The inverter's leakage-current sensor failed its own test at start-up. If a restart does not clear it the sensor or board inside has failed. Safe steps in the lookup |
Stop and call |
| ILeak-PROSolis ILeak-PRO | Leakage current protection[1] The inverter measured current leaking to earth from the solar wiring, usually damaged cable insulation, water in a connector, or a wiring problem on the AC side. Wet-morning alarms can be ageing panels, but any repeat needs an electrician because this is an electrical safety trip. Safe steps in the lookup |
Stop and call |
| L&PE FAULTSolis L&PE FAULT | AC line to earth fault[1] The inverter found a low resistance between the active and the earth on the AC side, which means a wiring or earth fault in the AC circuit. It needs an electrician. Safe steps in the lookup |
Stop and call |
| PV ISO-PROSolis PV ISO-PRO | Panel insulation fault[1] The inverter found too little insulation between the panel wiring and earth, usually water in a connector or isolator, a chafed cable or a damaged panel. Morning or wet-weather alarms that clear by midday point to moisture; a persistent one is a safety issue and needs an electrician. Safe steps in the lookup |
Stop and call |
| PvMidIsoSolis PvMidIso | Panel mid-point insulation low[1] The inverter found a low-insulation or earthed point part way along a panel string, often a wet connector or a damaged panel. Like any insulation fault, it needs testing by an electrician. Safe steps in the lookup |
Stop and call |
Over-temperature, heat derating and the cooling fans. Heat faults are taken seriously: a unit that cannot cool itself can be a fire risk. 1 stop and call, 1 wait and watch.
| Error code | What it means | What to do |
|---|---|---|
| OV-TEMSolis OV-TEM | Inverter too hot[1] The inverter's internal temperature went over its limit, so it cut back or stopped. Usually it is mounted in direct sun or a hot, closed space; it comes back once it cools, but if it happens on ordinary days the fan or heatsink needs a look. Heat shutdowns point at a failing fan, a blocked vent or a bad installation spot, so we treat them as a call. Safe steps in the lookup |
Stop and call |
| UN-TEMSolis UN-TEM | Inverter too cold[1] The inverter is below its minimum operating temperature and is waiting to warm up. It clears itself once the day warms. Safe steps in the lookup |
Wait and watch |
The unit's own electronics: relays, sensors, the DC bus, memory and its self-checks. Nearly all of these need an electrician. 11 stop and call, 1 worth a look.
| Error code | What it means | What to do |
|---|---|---|
| 12Power-FAULTSolis 12Power-FAULT | Internal 12V supply fault[1] The small power supply that runs the inverter's own electronics has failed. If a restart does not clear it the inverter needs repair. Safe steps in the lookup |
Stop and call |
| BoostFalSolis BoostFal | DC boost circuit fault[1] The circuit that lifts the panel voltage inside the inverter has failed its check. If a restart does not clear it, the inverter has an internal hardware fault. Safe steps in the lookup |
Stop and call |
| DCInj-FAULTSolis DCInj-FAULT | DC injection too high[1] The inverter is letting a small amount of DC into its AC output, which the grid rules do not allow. A one-off can clear with a restart; if it keeps coming back the output stage needs testing. DC on the AC side is a protection fault, so we treat it as a call. Safe steps in the lookup |
Stop and call |
| DSP-B-FAULTSolis DSP-B-FAULT | Internal processor fault[1] The inverter's two control processors have stopped talking to each other, or the control software is missing or does not match the hardware. If a restart does not clear it the control board has failed. Safe steps in the lookup |
Stop and call |
| IGBT-OV-ISolis IGBT-OV-I | Power stage overcurrent[1] The main switching transistors inside the inverter saw too much current. If a restart does not clear it the power board has failed. Safe steps in the lookup |
Stop and call |
| INI-FAULTSolis INI-FAULT | Start-up fault[1] The inverter's control processors did not agree with each other when it started up. If it stays stuck here after a restart the control board has a fault. Safe steps in the lookup |
Stop and call |
| OV-BUSSolis OV-BUS | Internal DC bus overvoltage[1] The voltage on the inverter's internal DC bus went too high. It can follow a string that is too long, but it is often a fault inside the inverter and needs testing. Safe steps in the lookup |
Stop and call |
| OV-G-ISolis OV-G-I | Grid output overcurrent[1] The inverter pushed more current into the grid than it is allowed to, often because the grid waveform is distorted or an AC connection is poor. A one-off clears itself; repeated alarms need a look at the AC side. Over-voltage, over-current and short-circuit faults can damage hardware, so we treat them as a call. Safe steps in the lookup |
Stop and call |
| RelayChk-FAILSolis RelayChk-FAIL | Output relay check failed[2][4] The relay that connects the inverter to the grid failed its self-test. Solis says to check the AC wiring and earthing first, but a repeat usually means the relay or power board has failed, which is a job for an electrician. Safe steps in the lookup |
Stop and call |
| UN-BUSSolis UN-BUS | Internal DC bus undervoltage[1] The voltage on the inverter's internal DC bus is too low. The manual puts it down to internal damage or a wire that has come loose, so it needs the inverter opened and tested. Safe steps in the lookup |
Stop and call |
| UNB-BUSSolis UNB-BUS | Internal DC bus unbalanced[1] The two halves of the inverter's internal DC bus are not sitting at the same voltage, which points to a failing component inside. It needs the inverter tested by an electrician. Safe steps in the lookup |
Stop and call |
| FailsafeSolis Failsafe | Export meter communication lost[1] The inverter has lost contact with the export-limit meter or EPM device, so it stops or limits output to be safe. The meter cable or setting needs checking. Safe steps in the lookup |
Worth a look |
The battery, its management system and its state of charge. These only appear on systems with a battery connected. 3 worth a look.
| Error code | What it means | What to do |
|---|---|---|
| CAN_Comm_FAILSolis CAN_Comm_FAIL | Battery communication fault[1] On a Solis hybrid, the inverter has lost contact with the battery or the battery is reporting an alarm. The battery cable, settings or the battery itself need checking. Safe steps in the lookup |
Worth a look |
| NO-BatterySolis NO-Battery | Battery not connected[1] On a Solis hybrid, the inverter cannot see the battery. Usually the battery breaker or fuse has tripped or the battery is switched off. Safe steps in the lookup |
Worth a look |
| OV-VbattSolis OV-Vbatt | Battery voltage out of range[1] On a Solis hybrid, the battery voltage is higher or lower than the inverter expects. A restart may clear it, otherwise the battery and its settings need checking. Safe steps in the lookup |
Worth a look |
No Solis error code matches that. Try the fault code lookup, which also works from a description of what you can see.
Our own licensed electricians cover Greater Adelaide and regional SA, and from North Brisbane up through the Sunshine Coast to Gympie. Check your postcode, then read us the code and tell us the install year. If it needs a visit, the callout is credited against the work.
Try one restart, in this order:
Never open the unit or touch the wiring. Never restart anything that smells hot or shows scorch marks. If the code comes back after one restart, stop and call.
On a visit, our electricians test the whole system before blaming the Solis. That means insulation resistance on every string, earth continuity, the grid relay, DC string voltages and currents, the AC supply at the switchboard and the inverter's own alarm history. RelayChk-FAIL is a good example: Solis says to check the AC wiring and earthing first, and only a repeat points at the relay or power board. G-IMP is often the cable run to the switchboard rather than the inverter.
Solis is supported in Australia through its local office, so when the fault is inside the unit we check whether a repair is possible before anything else. Some are and some are not. If the inverter cannot be fixed, we quote a straight replacement and a hybrid option side by side, and the callout comes off whichever you choose. The panels usually stay.
We do this work in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland only. Outside those areas, everything above still applies: take the code, its meaning and the urgency to a licensed electrician near you.
Every Solis code on this page was read from the maker's own manual. The numbers match the references in the code table.
Tables last updated
Read the alarm name exactly as the screen or SolisCloud spells it, dashes included, because OV-G-V and UN-G-V are opposite problems. Type it into the search box above the table, or scroll to the group it belongs to. Each row gives the plain-English meaning and one of three urgency ratings.
OV-G-V is “grid voltage too high”. The mains voltage at the inverter went above the limit it is allowed to export at, so it disconnected to protect itself. It usually clears on its own when the grid settles; if it happens most sunny afternoons the cable run or the street voltage needs checking. We rate it wait and watch. See it in the table.
ILeak-PRO is “leakage current protection”. The inverter measured current leaking to earth from the solar wiring, usually damaged cable insulation, water in a connector, or a wiring problem on the AC side. Wet-morning alarms can be ageing panels, but any repeat needs an electrician because this is an electrical safety trip. We rate it stop and call. See it in the table.
We work in Adelaide, the Adelaide Hills, Gawler, the Barossa, the Fleurieu, Murray Bridge and Yorke Peninsula in South Australia, or North Brisbane, Caboolture, Bribie Island, the Sunshine Coast, Noosa and Gympie in Queensland. Check your postcode to be sure. Outside those areas, this page still tells you what your code means and how urgent it is, and a licensed electrician near you can take it from there.
For homes in our service area, the phone diagnosis is free. If it needs a visit, there is a callout fee, and it is credited against any repair or replacement we do.
Yes, if it is in our service area. Most of our repair work is on systems someone else installed. We test the whole system, not just the unit on the wall.
The mains voltage at your inverter has gone above the limit it is allowed to export at, so it steps off the grid and reconnects once the voltage settles. Now and then is normal. If it happens most sunny afternoons, the cable run to the switchboard or the street voltage needs checking, and we test both on a visit.
Sometimes. Solis is still supported here, so a fault inside the unit is worth checking before anything is replaced, and many Solis alarms are outside the inverter altogether. We will tell you on the phone what your alarm usually means, and price a replacement beside any repair that is still possible.
From Solis’s own alarm code list in its service knowledge base and its S5 three-phase installation manual. Every Solis code on this page comes from the maker’s own documents, and each one carries a numbered reference to its document in the source list.
More solar repairs guides from our electricians.
Swipe to see more

All 34 SolaX error codes in plain English, for the X1 inverters and hybrids: what each one means, how urgent it is, how to reset your inverter safely, and whether it can still be repaired.
Read more
All 40 Sofar error codes in plain English, from ID01 to ID98: what each one means on a string inverter and on a HYD hybrid, how urgent it is, how to reset safely, and whether your inverter can still be repaired.
Read more$0 power bill guarantee
If you are considering solar for a new home, or on behalf of someone else, select "I own my home"
A solar or battery system is a permanent change to the property, so it needs to be arranged by the person who owns the home.
If you tapped that by mistake, head back and we'll pick up where you left off.
Our team can talk you through all options if you're not sure.
You'll get all of these. We'd just like to know what matters most.
The average Adelaide home spends $500 - $1000 per quarter. Not sure of yours? Take your best guess, we'll go through the real numbers at your assessment.
Whatever it is today, our goal is $0. If we don't get you there, we'll pay your bill.
We can work with you on a longer timeline, or get you saving as soon as possible.
We have hundreds of happy customers across South Australia. We need your address to check we service your area and to look at your roof before we visit.
Great news, we service your area!
Every system we design is tailored to the home, so the more info the better! (Optional)
Last step. We'll call to arrange your free on-site assessment at a time that suits you. No pressure and no obligation.
Request sent, we'll be in touch!
Call to speak directly with a solar specialist during business hours, and we can get your free on-site assessment booked in straight away.
📞If you haven't called already, we'll give you a call to say hello.
We'll chat about what you're looking for, how we can help, and book in a time for your on-site assessment that suits you.
We visit your home for 45 to 60 minutes to measure up the roof, check the switchboard and review how you use power.
A tailored proposal with the system design, the savings and the pricing laid out in full.
If you're happy with the proposal, our in-house team installs it and shows you how it all works.